康明斯发电机组控制器故障报警代码
康明斯发电机组控制器故障报警代码:
英文缩写 | 意义 | 英文缩写 | 意义 |
Wrn Oil Press | 低油压报警 | Unl Gen Overload | 发电机过载 |
Sd Oil Press | 低油压停机 | Unl Ineutral | 发电机中性线过流 |
Fls Oil Press | 油压传感器故障 | Sd AVR Fail | AVR故障 |
Wrn water Temp | 高水温报警 | Sd Overspeed | 超速停机 |
Sd Water Temp | 高水温停机 | Sd Underspeed | 低速停机 |
Fls Water Temp | 水温传感器故障 | Sd Start Fail | 启动失败 |
Wrn Fuel Level | 燃油位报警 | GCB Fail | 发电机开关故障 |
Sd Fuel Level | 燃油位停机 | MCB Fail | 市电开关故障 |
Fls Fuel Level | 燃油位传感器故障 | Gen set start | 油机启动 |
Wrn Batt Volt | 电池电压低报警 | Gen set stop | 油机停机 |
Emerg Stop | 急停 | Unl Back power | 逆功率故障 |
Wrn Charg Fail | 充电机故障报警 | GEN L1 neg | 发电机第一相相序错 |
Gen Undervolt | 发电机低电压 | GEN L2 neg | 发电机第二相相序错 |
Unl Vg1 Over | 发电机第一相过电压 | GEN L3 neg | 发电机第三相相序错 |
Unl Vg1 Under | 发电机第一相低电压 | G ph opposed | 发电机相序错 |
Unl Vg2 Over | 发电机第二相过电压 | G ph+L1 neg | |
Unl Vg2 Under | 发电机第二相低电压 | G ph+L2 neg | |
Unl Vg3 Over | 发电机第三相过电压 | G ph+L3 neg | |
Unl Vg3 Under | 发电机第三相低电压 | G phase Ang | |
Unl Fgen Over | 发电机频率过高 | Active Call | 有故障短信息 |
Unl Fgen Under | 发电机频率过低 | Bad Active Call | |
Unl Igen Unbal | 发电机三相电流不平衡 | SyncTimeout | 同步超时 |
Unl Vgen Unbal | 发电机三相电压不平衡 | R SyncTimeout | 同步超时 |
Unl Ig1 Over | 发电机第一相过电流 | Appl loaded | 控制器已初始化 |